NYKY-J

3 1/2-cores, 4 1/2-cores acc. to DIN VDE 0265


AT17_NYKY-J_en
VDE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optional

Standards

DIN VDE 0265 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in the ground, especially in applications where there is the influence of solvents, fuels, oils, gasoline or similar must be expected (e.g., refineries and gas stations).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
K lead sheath
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYKY-J 3x25 RM/16 RE


Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

3 1/2-cores, 4 1/2-cores acc. to DIN VDE 0265

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NYKY-J     3x25 RM/16 RE       0,6/1 kV 4337004 874 1290 29 2890 2.88 455 180 360
NYKY-J     3x35 RM/16 RE       0,6/1 kV 4336104 1162 1340 32 3400 4.03 605 190 380
NYKY-J     3x50 SM/25 RM       0,6/1 kV 4337604 1680 1680 34 4100 5.75 875 210 420
NYKY-J     3x70 SM/35 RM       0,6/1 kV 4337704 2352 2020 39 5310 8.05 1225 240 480
NYKY-J     3x95 SM/50 RM       0,6/1 kV 4350104 3216 2440 44 6850 10.93 1675 270 540
NYKY-J    3x120 SM/70 RM       0,6/1 kV 4337804 4128 2770 48 8350 13.80 2150 290 580
NYKY-J    3x150 SM/70 RM       0,6/1 kV 4338004 4992 3530 50 9730 17.25 2600 310 620
NYKY-J    3x185 SM/95 RM       0,6/1 kV 4338104 6240 4230 55 11805 21.28 3250 340 680
NYKY-J    3x240 SM/120 RM      0,6/1 kV 4338204 8064 5230 63 15045 27.60 4200 385 770
NYKY-J     4x25 RM/16 RE       0,6/1 kV 4335904 1114 1690 32 3520 2.88 580 200 400
NYKY-J     4x35 RM/16 RE       0,6/1 kV 4337904 1498 1785 34 4095 4.03 780 210 420
NYKY-J     4x50 RM/25 RM       0,6/1 kV 4335804 2140 2270 39 5205 5.75 1125 235 470
NYKY-J     4x70 RM/35 RM       0,6/1 kV 4335814 3082 2890 44 6930 8.05 0 0 0
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.