Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

multicore acc. to DIN VDE 0265


AT17_NYKY-J_en
VDE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!28-Ölbeständig50-Verlegung -5

 


Standards

DIN VDE 0265 and IEC 60502-1,
cores with black numbering printed.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1:1996 4H
 

Application

For indoor and outdoor installation, in the ground, especially in applications where there is the influence of solvents, fuels, oils, gasoline or similar must be expected (e.g., refineries and gas stations).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
K lead sheath
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYKY-J 5x1,5 RE 0,6/1 kV


Print Icon

BayEnergy® Power cables, PVC insulation, lead sheath, PVC sheath

NYKY-J

multicore acc. to DIN VDE 0265

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NYKY-J     7x1,5 RE   0,6/1 kV 4330700 101 545 17 890 0.17 53 100 200
NYKY-J     7x2,5 RE   0,6/1 kV 4332500 168 625 18 1030 0.29 88 110 220
NYKY-J       7x4 RE   0,6/1 kV 4332510 269 804 20 1330 0.46 140 120 240
NYKY-J     8x1,5 RE   0,6/1 kV 4331000 115 589 17 980 0.17 60 110 220
NYKY-J     8x2,5 RE   0,6/1 kV 4333900 192 643 19 1140 0.29 100 110 220
NYKY-J    10x1,5 RE   0,6/1 kV 4331200 144 680 20 1150 0.17 75 120 240
NYKY-J    10x2,5 RE   0,6/1 kV 4333000 240 865 21 1350 0.29 125 130 260
NYKY-J    12x1,5 RE   0,6/1 kV 4331700 173 710 20 1220 0.17 90 120 240
NYKY-J    12x2,5 RE   0,6/1 kV 4333100 288 940 22 1510 0.29 150 130 260
NYKY-J    14x1,5 RE   0,6/1 kV 4331100 202 735 21 1310 0.17 105 130 260
NYKY-J    14x2,5 RE   0,6/1 kV 4333200 336 980 23 1620 0.29 175 140 280
NYKY-J    16x1,5 RE   0,6/1 kV 4331800 230 853 22 1490 0.17 120 130 260
NYKY-J    16x2,5 RE   0,6/1 kV 4333300 384 1030 24 1850 0.29 200 150 300
NYKY-J    19x1,5 RE   0,6/1 kV 4332200 274 900 23 1600 0.17 143 140 280
NYKY-J    19x2,5 RE   0,6/1 kV 4333600 456 1170 25 2000 0.29 238 150 300
NYKY-J    21x1,5 RE   0,6/1 kV 4332300 302 980 25 1800 0.17 158 150 300
NYKY-J    21x2,5 RE   0,6/1 kV 4334000 504 1230 26 2140 0.29 263 160 320
NYKY-J      21x4 RE   0,6/1 kV 4334300 806 1557 31 2980 0.46 420 190 380
NYKY-J    24x1,5 RE   0,6/1 kV 4330100 346 1170 27 2010 0.17 180 160 320
NYKY-J    24x2,5 RE   0,6/1 kV 4334100 576 1370 29 2500 0.29 300 180 360
NYKY-J      24x4 RE   0,6/1 kV 4394800 922 1740 35 3570 0.46 480 210 420
NYKY-J    30x1,5 RE   0,6/1 kV 4332400 432 1240 28 2320 0.17 225 170 340
NYKY-J    30x2,5 RE   0,6/1 kV 4333700 720 1550 30 2780 0.29 375 180 360
NYKY-J    40x1,5 RE   0,6/1 kV 4332700 576 1390 31 2720 0.17 300 190 380
NYKY-J    40x2,5 RE   0,6/1 kV 4334500 960 1770 34 3430 0.29 500 200 400
NYKY-J    52x1,5 RE   0,6/1 kV 4332800 750 1640 34 3350 0.17 390 205 410
NYKY-J    52x2,5 RE   0,6/1 kV 4334200 1248 1826 38 4320 0.29 650 230 460
NYKY-J    61x1,5 RE   0,6/1 kV 4332900 880 2125 37 3780 0.17 458 220 440
NYKY-J    61x2,5 RE   0,6/1 kV 4334800 1464 2315 40 4760 0.29 763 240 480
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.