Print Icon

BayEnergy® Power cables, PVC insulation, armouring, PVC sheath

NYFGY-J

3-cores acc. to DIN VDE 0271


AT21_NYFGY-J_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt44-Nagetierschutz46-Robust50-Verlegung -5

 


Standards

DIN VDE 0271 and IEC 60502-1.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)


-5
+70

Max. permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max. 5s
 

Application

For indoor and outdoor installation, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where additional protection against mechanical damage is required and in the case of increased tensile forces during installation, laying and operation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y core insulation made of polyvinyl chloride (PVC)
FG flat steel wire armouring SWA, counter helix
Y outer sheath made of polyvinyl chloride (PVC)
J cable with green-yellow core
O cable without green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special Designs

Other designs, fitted lengths and larger delivery lengths on request.

Order Example

NYFGY-J 3 x 95 SM 0,6/1 kV (F 0,8v)


Print Icon

BayEnergy® Power cables, PVC insulation, armouring, PVC sheath

NYFGY-J

3-cores acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYFGY-J      3x50 SM   0,6/1kV  (F 0,8v) 4237014 1440 31 2600 5.75 830 190 380
NYFGY-J      3x70 SM   0,6/1kV  (F 0,8v) 4237124 2016 35 3400 8.05 1050 210 420
NYFGY-J      3x95 SM   0,6/1kV  (F 0,8v) 4237024 2874 40 4400 10.93 1350 240 480
NYFGY-J     3x120 SM   0,6/1kV  (F 0,8v) 4237134 3456 42 5200 13.80 1570 260 510
NYFGY-J     3x150 SM   0,6/1kV  (F 0,8v) 4237044 4320 49 6550 17.25 2100 300 600
NYFGY-J     3x185 SM   0,6/1kV  (F 0,8v) 4237144 5328 53 7900 21.28 2530 320 640
NYFGY-J     3x240 SM   0,6/1kV  (F 0,8v) 4237054 6912 59 9950 27.60 3050 360 720
NYFGY-J     3x300 SM   0,6/1kV  (F 0,8v) 4237154 8819 64 12050 34.50 3600 390 780
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.