Download IconPrint Icon

BayEnergy® Railway power cables, copper

NYSY 0,6/1 kV

Railway power cables 1kV acc. to DIN VDE 0271


AT363_NYSY_Bahnstrom_Cu_en
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse24-Flammwidrig50-Verlegung -5

optional

Längswasserdicht optionalHalogenfrei optionalRaucharm optionalÖlbeständig optionalUV-beständig optionalVerlegung -25 -30 -40 optional

Standards

DIN VDE 0271.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying C

-5
+70
Max permissible operating temperature
(conductor) °C
+70
Short-circuit temperature °C +160

Current carrying capacity, PVC-insulated cables
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s

 

Application

Cables for special applications, e.g. as a single-core railway traction current cable for direct current and alternating current. Also as a return current cable in direct current systems up to 0.6/1 KV.

Preferably for connections in overhead lines and rails, for laying in pipe conduits and trough channels and directly in the ground.

The regulations and standards of the transport services apply for the selection of railway traction current cables.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
S screen made of copper
Y outer sheath made of polyvinyl chloride (PVC)
v outer sheath reinforced
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYSY 1x400 RM/35 0,6/1 kV


Print Icon

BayEnergy® Railway power cables, copper

NYSY 0,6/1 kV

Railway power cables 1kV acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYSY      1x50 RM/16   0,6/1kV 4180020 635 18 855 5.75 250 130 260
NYSY      1x70 RM/16   0,6/1kV 4180010 849 19 1095 8.05 350 150 300
NYSY      1x95 RM/16   0,6/1kV 4180030 1121 22 1410 10.93 475 160 320
NYSY     1x120 RM/16   0,6/1kV 4180040 1377 23 1690 13.80 600 170 340
NYSY     1x150 RM/25   0,6/1kV 4180050 1754 25 2110 17.25 750 190 380
NYSY     1x185 RM/25   0,6/1kV 4180060 2134 27 2540 21.28 925 210 420
NYSY     1x240 RM/35   0,6/1kV 4185100 2815 31 3285 27.60 1200 230 460
NYSY     1x240 RM/25   0,6/1kV 4180070 2719 31 3190 27.60 1200 230 460
NYSY     1x300 RM/25   0,6/1kV 4185150 3338 33 3880 34.50 1500 250 500
NYSYv    1x300 RM/25   0,6/1kV 4185000 3338 35 4080 34.50 1500 270 540
NYSY     1x300 RM/35   0,6/1kV 4185160 3432 33 3570 34.50 1500 250 500
NYSY     1x400 RM/35   0,6/1kV 4185200 4477 37 5045 41.20 2000 280 560
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.