Print Icon

BayEnergy® Railway power cables, copper

(N)2XS2Y / (N)2XS(F)2Y
PE-Mantel

Railway power cables 1.8/3 kV acc. to IEC 60502-1, resp. based on DIN VDE 0271


AT371_N2XS_Bahnstrom_Cu_3kV_en
RoHS_LogoREACH_Logo

 

08-Trogverlegung04-Rohrverlegung02-Erdverlegung10-Verlegung im Freien, UV-Schutz beachten!23-Halogenfrei53-Verlegung -20

 


Standards

acc. to IEC 60502-1, based on DIN VDE 0271.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

The cables are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 1.8/3
Testing voltage kV 7
Cable temperature ºC
during laying (min)
after laying (max)

-20
+90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s
 

Application

Cables for special applications, e.g. as a single-core railway traction current cable for direct current and alternating current. Also as a return current cable in direct current systems up to 1.8/3 kV.

Preferably for connections in overhead lines and rails, for laying in pipe conduits and trough channels and directly in the ground.

The regulations and standards of the transport services apply for the selection of railway traction current cables.

Railway traction current cables with PVC sheath upon enquiry

Type Designation Codes

N cables acc. to standard
2X insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
(F) longitudinally watertight in the screen section
2Y outer sheath made of polyethylene (PE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

N2XS2Y 1x400 RM/16 1,8/3 kV
N2XS(F)2Y 1x400 RM/35 1,8/3 kV


Print Icon

BayEnergy® Railway power cables, copper

(N)2XS2Y / (N)2XS(F)2Y
PE-Mantel

Railway power cables 1.8/3 kV acc. to IEC 60502-1, resp. based on DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
(N)2XS2Y   1x95 RM/25  1,8/3kV  (A-NF) 4721700 1182 23 1365 13.59 475 170 340
(N)2XS2Y  1x150 RM/16  1,8/3kV  (A-NF) 4721800 1622 26 1815 21.45 750 190 380
(N)2XS2Y  1x150 RM/25  1,8/3kV  (A-NF) 4721840 1723 26 1920 21.45 750 200 400
(N)2XS2Y  1x185 RM/16  1,8/3kV  (A-NF) 4721810 1958 27 2170 0.00 925 210 410
(N)2XS2Y  1x185 RM/25  1,8/3kV  (A-NF) 4721850 2059 28 2260 26.46 925 210 410
(N)2XS2Y  1x240 RM/25  1,8/3kV  (A-NF) 4721820 2587 30 2795 34.32 1200 230 450
(N)2XS2Y  1x300 RM/25  1,8/3kV  (A-NF) 4721830 3163 32 3375 42.90 1500 240 480
(N)2XS2Y  1x300 RM/35  1,8/3kV  (A-NF) 4775400 3398 32 3620 42.90 1500 250 490
(N)2XS2Y  1x400 RM/35  1,8/3kV  (A-NF) 4775420 4234 35 4455 57.20 2000 270 540
(N)2XS2Y  1x500 RM/35  1,8/3kV  (A-NF) 4775410 5194 39 5445 71.50 2500 300 600
(N)2XS2Y  1x500 RM/50  1,8/3kV  (A-NF) 4726720 5360 40 5605 71.50 2500 300 600
(N)2XS(F)2Y   1x150 RM/16      1,8/3 kV   (A-NF) 4721410 1622 26 1825 21.45 750 200 390
(N)2XS(F)2Y   1x150 RM/25      1,8/3 kV   (A-NF) 4721420 1723 26 1925 21.45 750 200 400
(N)2XS(F)2Y   1x185 RM/16      1,8/3 kV   (A-NF) 4721430 1958 28 2160 26.46 925 210 410
(N)2XS(F)2Y   1x185 RM/25      1,8/3 kV   (A-NF) 4721440 2059 28 2265 26.46 925 210 420
(N)2XS(F)2Y   1x240 RM/25      1,8/3 kV   (A-NF) 4721450 2587 31 2800 34.32 1200 230 460
(N)2XS(F)2Y   1x300 RM/25      1,8/3 kV   (A-NF) 4721460 3163 33 3385 42.90 1500 250 490
(N)2XS(F)2Y   1x400 RM/35      1,8/3 kV   (A-NF) 4721400 4234 36 4455 57.20 2000 270 540
(N)2XS(F)2Y   1x500 RM/35      1,8/3 kV   (A-NF) 4721470 5194 40 5450 71.50 2500 300 600
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.