BayEnergy® Railway power cables, copper

(N)2XSH
flammwidrig

Railway power cables 1.8/3 kV acc. to IEC 60502-1, resp. based on DIN VDE 0271


AT371_N2XS_Bahnstrom_Cu_3kV_en
RoHS_LogoREACH_Logo

 

08-Trogverlegung04-Rohrverlegung02-Erdverlegung10-Verlegung im Freien, UV-Schutz beachten!50-Verlegung -5

 


Standards

acc. to IEC 60502-1, based on DIN VDE 0271.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

The cables are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 1.8/3
Testing voltage kV 7
Cable temperature ºC
during laying (min)
after laying (max)

-5
+90
Max permissible operating temperature
(conductor) °C
+90
Short-circuit temperature °C +250
Current carrying capacity
acc. to HD 603 S1-1994 5G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s
 

Application

Cables for special applications, e.g. as a single-core railway traction current cable for direct current and alternating current. Also as a return current cable in direct current systems up to 1.8/3 kV.

Preferably for connections in overhead lines and rails, for laying in pipe conduits and trough channels and directly in the ground.

The regulations and standards of the transport services apply for the selection of railway traction current cables.

Type Designation Codes

(N) cables based on to standard
2X insulation made of cross-linked polyethylene (XLPE)
S screen made of copper
Y outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

(N)2XSY 1x400 RM/16 1,8/3 kV


Print Icon

BayEnergy® Railway power cables, copper

(N)2XSH
flammwidrig

Railway power cables 1.8/3 kV acc. to IEC 60502-1, resp. based on DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
(N)2XSH  1x150 RM/16   1,8/3kV  (A-NF) 4722020 1622 25 1895 21.45 750 190 380
(N)2XSH  1x150 RM/25   1,8/3kV  (A-NF) 4722010 1723 26 2000 21.45 750 200 390
(N)2XSH  1x185 RM/16   1,8/3kV  (A-NF) 4722090 1958 27 2245 26.46 925 200 400
(N)2XSH  1x185 RM/25   1,8/3kV  (A-NF) 4722040 2059 27 2345 26.46 925 210 410
(N)2XSH  1x240 RM/25   1,8/3kV  (A-NF) 4722050 2587 30 2890 34.32 1200 230 450
(N)2XSH  1x300 RM/25   1,8/3kV  (A-NF) 4722060 3163 32 3485 42.90 1500 240 480
(N)2XSH  1x400 RM/35   1,8/3kV  (A-NF) 4722070 4234 35 4580 57.20 2000 270 530
(N)2XSH  1x500 RM/35   1,8/3kV  (A-NF) 4722080 5194 39 5595 71.50 2500 300 590
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.