Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, armouring, PVC sheath

NYFGY 3,6/6 kV

3-cores acc. to DIN VDE 0271


AT222_NYFGY_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt44-Nagetierschutz46-Robust50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0271.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 3.6/6
Testing voltage kV 11
Cable temperature ºC
during laying (min)
after laying (max)

-5
+70
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where additional protection against mechanical damage is required and in the case of increased tensile forces during installation, laying and operation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
FG flat steel wire armouring SWA, counter helix
Y outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, strand
SM sector-shaped conductor, strand

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYFGY 3 x 50 SM 3,6/6 kV


Print Icon

BayEnergy® Power cables, PVC insulation, armouring, PVC sheath

NYFGY 3,6/6 kV

3-cores acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYFGY       3x25 RM    3,6/6kV  (F 0,8v) 4811200 720 39 3050 2.88 1400 300 600
NYFGY       3x35 RM    3,6/6kV  (F 0,8v) 4811300 1008 42 3505 4.03 1550 320 630
NYFGY       3x50 SM    3,6/6kV  (F 0,8v) 4811600 1440 43 3795 5.75 1600 330 660
NYFGY       3x70 SM    3,6/6kV  (F 0,8v) 4820100 2016 46 4595 8.05 1900 350 700
NYFGY       3x95 SM    3,6/6kV  (F 0,8v) 4811800 2736 49 5550 10.93 2190 370 740
NYFGY      3x120 SM    3,6/6kV  (F 0,8v) 4811700 3456 52 6440 13.80 2500 400 800
NYFGY      3x150 SM    3,6/6kV  (F 0,8v) 4811400 4320 55 7430 17.25 2800 420 840
NYFGY      3x185 SM    3,6/6kV  (F 0,8v) 4812000 5328 62 9110 21.28 3150 465 930
NYFGY      3x240 SM    3,6/6kV  (F 0,8v) 4812200 6912 68 11270 27.60 4000 560 1020
NYFGY      3x300 SM    3,6/6kV  (F 0,8v) 4812300 8819 68 12590 34.50 4200 520 1030
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.