Download IconPrint Icon

BayEnergy® Power cables, PVC insulation, armouring, PVC sheath

NYFGY 3,6/6 kV

3-cores acc. to DIN VDE 0271


AT222_NYFGY_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung16-Inhouse10-Verlegung im Freien, UV-Schutz beachten!30-Ölbeständig_bedingt44-Nagetierschutz46-Robust50-Verlegung -5

 


Standards

DIN VDE 0271.

The cables are in compliance with RoHS Directive EU 2011/65/EU - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 3.6/6
Testing voltage kV 11
Cable temperature ºC
during laying (min)
after laying (max)

-5
+70
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where additional protection against mechanical damage is required and in the case of increased tensile forces during installation, laying and operation.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
FG flat steel wire armouring SWA, counter helix
Y outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, strand
SM sector-shaped conductor, strand

Order Example

NYFGY 3 x 50 SM 3,6/6 kV


Print Icon

BayEnergy® Power cables, PVC insulation, armouring, PVC sheath

NYFGY 3,6/6 kV

3-cores acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYFGY      3x25 RM    3,6/6 kV  (F 0,8v) 4811200 720 39 3050 2.88 1400 300 600
NYFGY      3x35 RM    3,6/6 kV  (F 0,8v) 4811300 1008 42 3505 4.03 1550 320 630
NYFGY      3x50 SM    3,6/6 kV  (F 0,8v) 4811600 1440 44 3850 5.75 1600 330 660
NYFGY      3x70 SM    3,6/6 kV  (F 0,8v) 4820100 2016 48 4660 8.05 2000 360 720
NYFGY      3x95 SM    3,6/6 kV  (F 0,8v) 4811800 2736 51 5720 10.93 2200 390 780
NYFGY     3x120 SM    3,6/6 kV  (F 0,8v) 4811700 3456 54 6610 13.80 2500 410 820
NYFGY     3x150 SM    3,6/6 kV  (F 0,8v) 4811400 4320 58 7640 17.25 2900 440 880
NYFGY     3x185 SM    3,6/6 kV  (F 0,8v) 4812000 5328 63 9120 24.28 3500 480 960
NYFGY     3x240 SM    3,6/6 kV  (F 0,8v) 4812200 6912 68 11160 27.60 4000 510 1020
NYFGY     3x300 SM    3,6/6 kV  (F 0,8v) 4812300 8819 72 13220 34.50 4500 540 1080
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.