Print Icon

BayEnergy® Power cables, PVC insulation, screen, PVC sheath

NYSY 3,6/6 kV

1-core acc. to DIN VDE 0271


AT30_NYSY_6kV_en
VDE_LogoRoHS_LogoREACH_Logo

 

02-Erdverlegung08-Trogverlegung04-Rohrverlegung10-Verlegung im Freien, UV-Schutz beachten!16-Inhouse30-Ölbeständig_bedingt50-Verlegung -5

optional

Verlegung -25 -30 -40 optionalUV-beständig optionalÖlbeständig optional

Standards

DIN VDE 0271.

The cables are in compliance with RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 3.6/6
Testing voltage kV 11
Cable temperature ºC
during laying (min)
after laying (max)

-5
+70
Max permissible operating temperature (conductor) °C +70
Short-circuit temperature °C +160
Current carrying capacity
acc. to HD 603 S1-1994 3G23
during regular operation: table 14+15
in case of short-circuit: table 17
short-circuit duration max 5s
 

Application

For indoor installation and in cable ducts, in open air, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage.

The cables are insensitive to occasional impacts of oils and fuels.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
Y insulation made of polyvinyl chloride (PVC)
S screen made of copper
Y outer sheath made of polyvinyl chloride (PVC)
v outer sheath reinforced
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NYSY 1 x 500 RM/35 3,6/6 kV


Print Icon

BayEnergy® Power cables, PVC insulation, screen, PVC sheath

NYSY 3,6/6 kV

1-core acc. to DIN VDE 0271

Product Bayka Order No. Cu No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km mm kg/km kA daN min. mm min. mm  
NYSYv     1x240 RM/25  3,6/6kV 4684500 2570 34 3115 27.60 1200 260 520
NYSY      1x300 RM/25  3,6/6kV 4684510 3163 35 3615 0.00 1500 270 540
(N)YSYv   1x500 RM/35  3,6/6kV  (M-SW / Wd>3,1) 4688400 5194 43 5865 0.00 2500 440 880
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.