Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBA

3-cores 12/20 kV acc. to DIN VDE 0276-621


ET15_en
VDE_Logo

Standards

According to DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 12/20
Testing voltage kV 32
Cable temperature ºC
during laying (min)
after laying (max)


+5
+65

Max permissible operating temperature (conductor) °C +65
Short-circuit temperature °C +170
Current carrying capacity
acc. to HD 621 S1:1996 4C
during regular operation: table 11
in case of short-circuit: table 14
short-circuit duration max 5s
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
E cores individually enclosed with metal sheath and corrosion protection, and stranded
K lead sheath
E protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils
B armouring made of steel tape
A sheath and/or outer sheath made of fibrous material
RM circular conductor, stranded
ND or H
cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NEKEBA 3 x 150 RM 12/20 kV


Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBA

3-cores 12/20 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NEKEBA    3x25 RM     12/20 kV 3411500 720 2770 56 6950 3.00 375 420 840
NEKEBA    3x35 RM     12/20 kV 3411600 1008 2940 58 7520 4.20 525 440 880
NEKEBA    3x50 RM     12/20 kV 3411700 1440 3120 60 8210 6.00 750 460 920
NEKEBA    3x70 RM     12/20 kV 3411800 2016 3660 65 9550 8.40 1050 490 980
NEKEBA    3x95 RM     12/20 kV 3412000 2736 3920 69 11610 11.40 1425 520 1040
NEKEBA    3x95 RM     12/20 kV 3412001 2736 3920 69 11305 11.40 1425 520 1040
NEKEBA   3x120 RM     12/20 kV 3412100 3456 4160 72 12900 14.40 1800 550 1100
NEKEBA   3x150 RM     12/20 kV 3412600 4320 4740 76 14540 18.00 2250 570 1140
NEKEBA   3x185 RM     12/20 kV 3412300 5328 5020 79 16100 22.20 2775 600 1200
NEKEBA   3x240 RM     12/20 kV 3412400 6912 5460 85 18520 28.80 3600 640 1280
NEKEBA   3x300 RM     12/20 kV 3412500 8640 6220 89 21250 36.00 3600 680 1360
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.