Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBA

3-cores 18/30 kV acc. to DIN VDE 0276-621


ET15_en
VDE_Logo

Standards

According to DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 18/30
Testing voltage kV 47
Cable temperature ºC
during laying
after laying


+5 to +65
-30 to +65

Max permissible operating temperature (conductor) °C +65
Short-circuit temperature °C +170
acc. to HD 621 S1-1996 4C21
during regular operation: table 11+12
in case of short-circuit: table 14
short-circuit duration max 5s.
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
E cores individually enclosed with metal sheath and corrosion protection, and stranded
K lead sheath
E protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils
B armouring made of steel tape
A sheath and/or outer sheath made of fibrous material
RM circular conductor, stranded
ND or H
cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NEKEBA 3 x 150 RM 18/30 kV


Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBA

3-cores 18/30 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NEKEBA    3x95 RM      18/30kV 3414300 2736 4920 81 13500 11.11 1425 610 1215
NEKEBA   3x120 RM      18/30kV 3414400 3456 5180 82 14700 14.04 1800 625 1245
NEKEBA   3x150 RM      18/30kV 3433900 4320 5450 88 16000 17.55 2250 660 1320
NEKEBA   3x185 RM      18/30kV 3434000 5328 6130 90 17915 21.65 2775 675 1350
NEKEBA   3x240 RM      18/30kV 3414500 6912 6600 95 20480 28.08 3600 715 1425
NEKEBA   3x300 RM      18/30kV 3414600 8640 7430 99 23650 28.08 4500 750 1500
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.