Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBY

3-cores 12/20 kV acc. to DIN VDE 0276-621


ET16_NEKEBY
VDE_Logo

Standards

According to DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 12/20
Testing voltage kV 32
Cable temperature ºC
during laying (min)
after laying (max)


+5
+65

Max permissible operating temperature (conductor) °C +65
Short-circuit temperature °C +170
Current carrying capacity
acc. to HD 621 S1:1996 4C
during regular operation: table 11
in case of short-circuit: table 14
short-circuit duration max 5s
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
E cores individually enclosed with metal sheath and corrosion protection, and stranded
K lead sheath
E protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils
B armouring made of steel tape
Y sheath and/or outer sheath made of polyvinyl chloride (PVC)
RM circular conductor, stranded
ND or H
cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NEKEBY 3x150 RM 12/20 kV


Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, copper

NEKEBY

3-cores 12/20 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius repeated Bending radius one-off
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NEKEBY    3x25 RM      12/20kV 3412700 720 2770 60 7470 3.00 375 900 450
NEKEBY    3x35 RM      12/20kV 3412800 1008 2940 60 7850 4.20 525 920 460
NEKEBY    3x50 RM      12/20kV 3412900 1440 3120 64 8835 6.00 750 975 490
NEKEBY    3x50 RM -H-  12/20kV 3412910 1440 3120 64 8835 6.00 750 975 490
NEKEBY    3x70 RM      12/20kV 3413000 2016 3660 70 10955 8.40 1050 1065 535
NEKEBY    3x95 RM      12/20kV 3413100 2736 3920 74 12425 7.60 1425 1110 555
NEKEBY   3x120 RM      12/20kV 3413200 3456 4160 77 13765 14.40 1800 1170 585
NEKEBY   3x150 RM      12/20kV 3441300 4320 4740 82 15625 18.00 2250 1230 615
NEKEBY   3x185 RM      12/20kV 3413400 5328 5020 85 17290 22.20 2775 1275 640
NEKEBY   3x240 RM      12/20kV 3413500 6912 5460 91 19940 28.80 360 1365 685
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.