Print Icon

BayEnergy® Paper insulated cables, belted cable, aluminium

NAKBY

3-cores 3,6/6 kV acc. to DIN VDE 0276-621


ET21_NAKBY
VDE_Logo

Standards

See DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 3.6/6
Testing voltage kV 11.5
Cable temperature ºC
during laying (min)
after laying (max)

+5
+65
Max permissible operating temperature (conductor) °C +65
Short-circuit temperature °C +170
Current carrying capacity
acc. to HD 621 S1:1996 4C
during regular operation: table 11
in case of short-circuit: table 5
short-circuit duration max 5s
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
K lead sheath
B armouring made of steel tape
Y sheath and/or outer sheath made of polyvinyl chloride (PVC)
SM sector-shaped conductor, stranded
ND
or H

cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NAKBY 3x95 SM 3,6/6 kV


Print Icon

BayEnergy® Paper insulated cables, belted cable, aluminium

NAKBY

3-cores 3,6/6 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Al-No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NAKBY    3x95 SM      3,6/6 kV 3307000 827 2210 50 5400 7.60 855 450 900
NAKBY   3x120 SM      3,6/6 kV 3307200 1044 2490 53 6800 9.60 1080 480 960
NAKBY   3x150 SM      3,6/6 kV 3307300 1305 2840 56 7700 12.00 1350 555 1010
NAKBY   3x185 SM      3,6/6 kV 3307400 1610 3600 60 8700 14.80 1665 540 1080
NAKBY   3x240 SM      3,6/6 kV 3307100 2088 3900 64 10000 19.20 2160 580 1160
NAKBY   3x300 SM      3,6/6 kV 3304500 2610 4400 72 11745 24.00 2700 650 1300
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.