Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, aluminium

NAEKEBA

3-cores 18/30 kV acc. to DIN VDE 0276-621


ET24_25_NAEKEBA_NAEKEBY_de
VDE_Logo

Standards

According to DIN VDE 0276-621.

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 18/30
Testing voltage kV 47
Cable temperature ºC
during laying (min)
after laying (max)


+5
  +60

Max permissible operating temperature (conductor) °C +60
Short-circuit temperature °C +150
Current carrying capacity
acc. to HD 621 S1:1996 4C
during regular operation: table 11
in case of short-circuit: table 14
short-circuit duration max 5s
 

Application

In the ground, in open air, for indoor installation and in cable ducts, where no particular mechanical loads are expected (see DIN VDE 0298-1).

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
A conductor made of aluminium
E cores individually enclosed with metal sheath and corrosion protection, and stranded
K lead sheath
E protective sheath with embedded layer (e.g. wrapping) made of elastomer tape or plastic foils
B Bewehrung aus Stahlbandarmouring made of steel tape
A sheath and/or outer sheath made of fibrous material
RM circular conductor, stranded
ND or H
cable with adhesive mass (non-drain)

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NAEKEBA 3x150 RM 18/30 kV


Print Icon

BayEnergy® Paper insulated cables, 3-cores with single lead sheath, aluminium

NAEKEBA

3-cores 18/30 kV acc. to DIN VDE 0276-621

Product Bayka Order No. Al-No. Pb No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km kA daN min. mm min. mm  
NAEKEBA   3x70 RM      18/30kV 3459000 609 4770 76 10665 5.39 630 570 1140
NAEKEBA   3x95 RM      18/30kV 3450000 827 4920 79 11520 7.32 855 600 1200
NAEKEBA  3x120 RM      18/30kV 3450100 1044 5180 84 12800 9.24 1080 630 1260
NAEKEBA  3x150 RM      18/30kV 3450200 1305 5450 86 14110 11.55 1350 660 1320
NAEKEBA  3x185 RM      18/30kV 3456400 1610 6130 90 14465 14.25 1665 675 1350
NAEKEBA  3x240 RM      18/30kV 3445500 2088 6600 95 15955 18.48 2160 715 1430
NAEKEBA  3x240 RM  H   18/30kV 3464100 2088 6600 95 15955 18.48 2160 715 1430
NAEKEBA  3x300 RM      18/30kV 3445700 2610 7430 100 18195 23.10 2700 750 1500
NAEKEBA  3x400 RM      18/30kV 3445800 3480 10005 114 20535 30.80 3600 855 1710
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.