Download IconPrint Icon

BayEnergy® Copper ropes, lead sheath

Cu-Pb-Seile
NB

bare with lead-sheath Conductor acc. to DIN EN 60228 (VDE 0295)


FT201
VDE_LogoCE_Logo

Standards

DIN VDE 0295 (for the conductor)

Technical Data

Conductor made of copper, bare and/or tin-coated  
Stranded conductor design, uncompressed Conductor class 2
Lead sheath  

Application

For indoor installation, in the open air and in the ground, as lightning rod for industrial plants and buildings, especially in applications where there is the influence of solvents, fuels, oils, gasoline or similar must be expected (e.g., refineries and gas stations).
The lead sheath is insensitive to humic acid and aggressive soil components.cables acc. to standard

Type Designation Codes

N cables acc. to standard
B lead sheath
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NB 1 x 50 RM 0,6/1 kV


Print Icon

BayEnergy® Copper ropes, lead sheath

Cu-Pb-Seile
NB

bare with lead-sheath Conductor acc. to DIN EN 60228 (VDE 0295)

Product Bayka Order No. Cu No. Pb No. Outer ∅
approx.
Net weight
approx.
Max. tensile force Bending radius one-off Bending radius repeated
kg/km kg/km mm kg/km daN min. mm min. mm  
NB     1x50 RMv-blw  (Pb 1,20) 3027800 480 436 11 916 250 170 340
NB     1x50 RMv-blw  (Pb 2,00) 3027900 480 841 13 1321 250 190 380
NB     1x70 RMv-blw  (Pb 1,20) 3028200 672 539 13 1211 350 190 380
NB     1x70 RMv-blw  (Pb 1,00) 3028100 672 442 13 1114 350 190 380
NB     1x95 RMv-blw  (Pb 1,20) 3028700 912 622 15 1534 475 220 440
NB    1x120 RMv-blw  (Pb 1,20) 3029500 1152 694 16 1846 600 240 480
NB    1x150 RMv-blw  (Pb 1,20) 3030000 1440 758 18 2198 750 260 520
NB    1x185 RMv-blw  (Pb 1,20) 3030510 1776 840 19 2616 925 290 580
NB    1x240 RMv-blw  (Pb 1,20) 3030800 2304 961 22 3265 1200 320 640
NB    1x240 RMv-blw  (Pb 1,65) 3031020 2304 1496 22 3800 1200 340 680
NB    1x400 RMv-blw  (Pb 2,00) 3031210 3840 2097 28 5937 2000 420 840
NB    1x400 RMv-blw  (Pb 1,50) 3031230 3840 1540 27 5380 2000 400 800
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
On customer request, another structure of the conductor is possible.