Download IconPrint Icon

BayEnergy® XLPE insulated overhead lines

NFA2X

1-6-cores acc. to DIN VDE 0276-626


FT10_NFA2X_de
VDE_LogoRoHS_LogoREACH_LogoCE_Logo

 

12-Luftkabel08-Trogverlegung04-Rohrverlegung20-UV-beständig23-Halogenfrei53-Verlegung -20

 


Standards

DIN VDE 0276 - 626.

The cables are in compliance with EU LVD (Low Voltage Directive 2014/35/EU) and RoHS Directive EU 2002/65/EC - RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.

Technical Data

Rated voltage kV 0.6/1
Testing voltage kV 4
Cable temperature ºC
during laying (min)
after laying (max)

-20 to +50
  +80
Max permissible operating temperature (conductor) °C +80
Short-circuit temperature °C +130

Application

XLPE-insulated overhead line are used in open air for permanent laying on posts (e.g. in densely populated building areas or forests, where the use of bare overhead lines is not economical). They can also be laid along walls or ceilings with and without stress relief in special cases.

Laying of XLPE-insulated overhead lines in not permissible in the ground.

The cables are halogen-free and UV-resistant.

Type Designation Codes

N cables acc. to standard
(N) cables based on standard
F stranded overhead line
A conductor made of aluminium
2X core insulation made of cross-linked polyethylene (XLPE)
RM circular conductor, stranded

Special Designs

Design according to national and international standards
Design according to customer specifications
Design with limited tolerance of outer diameter on request

Order Example

NFA2X 4 x 50 RM 0,6/1 kV


Print Icon

BayEnergy® XLPE insulated overhead lines

NFA2X

1-6-cores acc. to DIN VDE 0276-626

Product Bayka Order No. Al-No. Outer ∅
approx.
Net weight
approx.
Rated short-time current Bending radius one-off Bending radius repeated
kg/km mm kg/km kA min. mm min. mm  
NFA2X       1x25 RM    0,6/1kV 4789900 72 9 100 2.35 70 140
NFA2X       1x35 RM    0,6/1kV 4790000 102 10 130 3.29 75 150
NFA2X       1x35 RM    0,6/1kV    (1 NOPPE) 4790100 102 10 130 0.00 0 0
NFA2X       1x35 RM    0,6/1kV    (2 NOPPEN) 4792200 102 10 130 0.00 0 0
NFA2X       1x35 RM    0,6/1kV    (3 NOPPEN) 4792300 102 10 130 0.00 0 0
NFA2X       1x50 RM    0,6/1kV 4789800 145 11 180 0.00 0 0
NFA2X       1x70 RM    0,6/1kV 4790300 203 13 240 6.58 100 200
NFA2X       1x70 RM    0,6/1kV 4790301 203 13 230 6.58 100 200
NFA2X       4x25 RM    0,6/1kV 4790500 290 21 390 2.35 130 260
NFA2X       4x25 RM    0,6/1kV 4790510 290 21 390 2.35 130 260
NFA2X       4x35 RM    0,6/1kV 4791600 406 24 525 3.29 145 290
NFA2X        4x35 RM + 1x25 RM      0,6/1kV 4791700 478 25 620 3.29 160 320
(N)FA2X      4x35 RM + 1x35 RM      0,6/1kV 4791800 508 26 655 3.29 165 330
NFA2X       4x50 RM    0,6/1kV 4790700 580 27 720 4.70 170 340
NFA2X       4x70 RM    0,6/1kV 4790800 812 31 960 6.58 195 390
NFA2X        4x70 RM + 1x35 RM      0,6/1kV 4791100 914 35 1090 6.58 210 420
NFA2X        4x70 RM + 2x35 RM      0,6/1kV 4791200 1016 38 1220 6.58 235 470
NFA2X        4x70 RM + 2x25 RM      0,6/1kV 4791110 956 37 1150 6.58 230 460
NFA2X        4x70 RM + 1x25 RM      0,6/1kV 4791220 884 34 1050 6.58 210 420
(N)FA2X     4x95 RM    0,6/1kV 4790900 1102 37 1340 8.93 0 0
(N)FA2X      4x95 RM + 1x35 RM      0,6/1kV 4792000 1204 39 1470 8.93 235 470
(N)FA2X      4x95 RM + 1x25 RM      0,6/1kV 4792110 1175 37 1430 8.93 230 460
Errors and omissions excepted, weights and dimensions are approximate values.
Other designs, fitted lengths and larger delivery lengths on request.
The bending radius one-off is for professionally installed cables, unique molding.
The bending radius repeated applies to dynamic bending operations eg during the installation.