BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath
NYCY
2-3-cores acc. to DIN VDE 0276












Standards
DIN VDE 0276-603 part 3G / HD 603.1 and IEC 60502-1.
The cables are in compliance with EU LVD (Low Voltage Directive) and RoHS Directive (Restriction of Hazardous Substances) and REACH (European Chemicals Regulation).
They are flame retardant and self-extinguishing according to DIN EN 60332-1-2 (EN 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting properties of lacquers.
Technical Data
Rated voltage kV | 0.6/1 |
Testing voltage kV | 4 |
Cable temperature ºC during laying (min) after laying (max) |
|
Max. permissible operating temperature (conductor) °C | +70 |
Short-circuit temperature °C | +160 |
Current carrying capacity acc. to HD 603 S1-1994 3G during regular operation: table 14+15 in case of short-circuit: table 17 short-circuit duration max. 5s |
Application
For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where protection against contact voltage is required in the case of mechanical damage. (See DIN VDE 0298-1.)
The cables are insensitive to occasional impacts of oils and fuels.
Type Designation Codes
N | cables acc. to standard |
(N) | cables based on standard |
Y | insulation made of polyvinyl chloride (PVC) |
C | Concentric Cu-conductor |
Y | outer sheath made of polyvinyl chloride (PVC) |
J | cable with green-yellow core |
O | cable without green-yellow core |
RE | circular conductor, solid |
RM | circular conductor, stranded |
SM | sector-shaped conductor, stranded |
Order Example
NYCY 3 x 6 RE/6 0,6/1 kV
BayEnergy® Power cables, PVC insulation, concentric conductor, PVC sheath
NYCY
2-3-cores acc. to DIN VDE 0276
Other designs, fitted lengths and larger delivery lengths on request.
Tensile force only valid when cable sheath and cable core involved.
The bending radius one-off is for professionally installed cables, unique molding over a stencil and a cable temperature >30 ° C.
*) CPR Construction Products Regulation Class,
DoP Declaration of Performance.
The DoP applies exclusively to Bayka cables.